Description:
It's suitable for the power system with three-phase AC 50 Hz and rated voltage of 12KV. The permanent magnet switch is mainly used as a substation 10KV outlet switch and a line protection switch for closing and opening load current, breaking overload current and short circuit current in 10KV three- -phase AC power system.ZW43- 12(G)/M630- -20 type outdoor High Voltage Permanent Magnet vacuum Circuit Breaker (Hereinafter called permanent magnet switch) is suitable for the power system with three-phase AC 50 Hz and rated voltage of 12KV. The permanent magnet switch is mainly used as a substation 10KV outlet switch and a line protection switch for closing and opening load current, breaking overload current and short circuit current in 10KV three- -phase AC power system. The circuit breaker complies with GB1984- -2003 "High Voltage AC Circuit Breaker'", DL/T402 -2007 "High Voltage AC Circuit Breaker Ordering Technical Conditions", DL/T403- -2000 "12KV~40.5KV High Voltage Vacuum Circuit Breaker Ordering Technical Conditions" and other technical standards.
Model Meaning

Working Condition
O Ambient temperature: -409~+40C. O Altitude: <≤3000mm. OWind pressure: Not more than 700Pa(Equivalent to wind speed 34m/s). O Pollution level: Not more than IV. OPlace should be no fire, explosion hazard, chemical corrosion and severe vibration,etc.
Drawing

No | ltem | Unit | Data | ||
1 | Rated voltage | KV | 12 | ||
2 | Rated insulation level | 1 min power frequency withstand voltage | Dry test (phase to phase,to earth,Between open contacts) | 42/48 | |
Wet test | 34 | ||||
Lightning impulse withstand voltage (peak,phase to phase,between open contacts) | 75/85 | ||||
3 | Rated Current | A | 630 | ||
4 | Rated short circuit breaking current | KA | 20 | ||
5 | Rated operating sequence | O~0.3-CO-180s-COS | |||
6 | Rated short-circuit breaking current breaking time | Times | 30 | ||
7 | Rated short circuit closing current(peak) | KA | 50 | ||
8 | Rated peak withstand current | ||||
9 | Rated short-time withstand current | 20 | |||
10 | Rated short circuit duration | S | 4 | ||
11 | Opening time (The time from the control unit to receiving the opening command to the separation of the three- phase contact) | 0.040~0.060 | |||
12 | Closing time(The time from the control unit to receiving the closing command to the closing time of the three- phase contact | 0.070-0.120 | |||
13 | Mechanical life | Times | 10.000 | ||
14 | Rated closing operating voltage | V | DC110 | ||
15 | Rated opening operating voltage | DC110 | |||
16 | Overcurrent protection | Current setting multiple | 0.2~2.5 | ||
Setting the allowable error of the current | ±10% | ||||
Delay setting | S | 0~5 | |||
Delay allowed error | ±10% | ||||
17 | Quick break protection | Current setling multiple | 2.5~10 | ||
Setting the allowable error of the current | ±10% | ||||
Delay setting | S | 0~0.5 | |||
Delay allowed error | ±10% | ||||
18 | Control unit AC charging input current | Rating | A | 5 | |
Fluctuation range | A | 0.5~8 | |||
Copyright © 2025 Boxd Group Co., Ltd.
This website uses cookies to ensure you get the best experience on our website.
Comment
(0)