Description:
The circuit breaker is mainly used for breaking and closing the load current, overload current and short- -circuit current in the power system. It is suitable for protection and control in substation and industrial and mining enterprise power distribution system, and the place where rural power grid needs frequent operation.ZW32M-12 outdoor permanent magnet high voltage AC vacuum Circuit Breaker (hereinafter called smart switch) consists of ZW32-12/T630-20 outdoor high voltage Vacuum Circuit Breaker, reclosing controller, external voltage transformer and control cable. The smart switch is an outdoor high- -voltage power distribution Switchgear device with rated voltage of 12 KV and three- -phase AC of 50 Hz. The circuit breaker is mainly used for breaking and closing the load current, overload current and short- -circuit current in the power system. It is suitable for protection and control in substation and industrial and mining enterprise power distribution system, and the place where rural power grid needs frequent operation. The smart switch complies with GB 1894 -2003 "High Voltage AC Circuit Breaker" and GB/T 7261-2008 "Basic Test Methods for Relay Protection and Safety Automatic Devices" and other standards
Model Meaning

Working Condition
O Ambient air temperature: Max. +45C ,Min.-40%C. O Altitude:≤3000m. O Wind speed: Not more than 34m/s. O Relative Air Humidity: Daily average is not greater than 90%, month average is not greater than 90%. O Pollution level: Not more than IV. O lcing thickness:≤10mm. O Installation site: should be no fire, explosion hazard, chemical corrosion and severe vibration,etc.
Drawing

No | Item | Unit | Data | ||
1 | Rated voltage | KV | 12 | ||
2 | Rated current | A | 630 | ||
3 | Rated frequency | Hz | 50 | ||
4 | Rated insulation level | 1 min power frequency withstand voltage (to earth, phase to phase,between open contacts) | Dry test | KV | 42/48(Between open contacts) |
Wet test | 34 | ||||
Secondary circuit to earth | 2 | ||||
Lightning impulse withstand voltage (peak) | 75/85(Between open contacts) | ||||
5 | Rated short circuit breaking current | KA | 20 | ||
6 | Rated short-circuit closing current (peak) | KA | 50 | ||
7 | Rated short-circuit withstand current | KA | 20 | ||
8 | Rated peak withstand current | KA | 50 | ||
9 | Rated short-circuit breaking current breaking times | Times | 30 | ||
10 | Rated short circuit duration | S | 4 | ||
11 | Rated operating voltage and auxiliary voltage | V | DC220 or AC220 | ||
12 | Rated operating sequence | O-0.3s-CO-180s-CO | |||
13 | Overcurrent release rated current | A | 5 | ||
14 | Mechanical life | Times | 10000 | ||