ZN28-12 Indoor Vacuum Circuit Breaker

Description:

• Classification Series :Indoor Vacuum Circuit Breaker • Product Name :ZN28-12 Indoor Vacuum Circuit Breaker • Product Overview: Auxiliary power protection for incoming/outgoing lines of 12kV distribution system, distribution stations of industrial and mining enterprises and power plants (suitable for switchgear such as KYN28A-12 and XGN2-12)...
  • Detailed Description
  • Model meaning

    Z: Vacuum Interruption

    N: Indoor installation (indoor)

    28: Design serial number

    12: Rated voltage (kV)

     

    Core function

    Full current interrupting: safely interrupt rated current, overload current and short circuit current (up to 31.5kA).

    Quick protection: the opening time is ≤60ms, and the fault current is cut off.

     

    Typical application

    Auxiliary power protection for incoming/outgoing lines of 12kV distribution system, distribution stations of industrial and mining enterprises and power plants (suitable for Switchgear such as KYN28A-12 and XGN2-12).

     

    Selection formula

    Short-circuit verification: the expected short-circuit current of the system is less than or equal to the rated breaking current (Isc) of the Circuit Breaker.

    Continuous current: maximum load current × 1.2 ≤ rated current (Ir)

    Altitude correction: When it is more than 1000m, the volume of Ir decreases by 1% for every 100m increase.

     

    Mechanical characteristic monitoring

    Key indicators: opening speed (1.2 0.2m/s) and overtravel (4±0.5mm).

    Abnormal threshold: speed drop > 15% or overtravel < 3mm → overhaul immediately.

     

    Periodic maintenance

    3 years /3000 operations:

    Measure the resistance of the main circuit (standard: ≤45μΩ @ 1250A)

    Check the contact wear (allowable wear ≤3mm)

    10 years: replace the vacuum interrupter (compulsory scrapping cycle)

     

    Safety specification

    When operating, it must be in the test position/working position, and it is forbidden to open and close in the intermediate state.

     

     